Skip to the tool
makeshortwork.com Insulation R-Value Calculator

Insulation R-Value Calculator

Stack the assembly the way it is actually built — cladding, sheathing, cavity insulation, drywall, air films — and get the total R-value, the U-factor, the metric RSI, and the effective R after the framing has taken its cut.

The assembly
Layers, outside to inside
Framing / thermal bridging
Share of the wall area that is structure, not cavity. Whole-wall values include studs, plates, corners and headers — that is why 16 in spacing gives 25%, not 11%.
Climate and energy
Pre-filled with the IECC prescriptive value for this zone and element.

This assembly

Effective R-value
By thickness
By share of R
Same layers, two scales. Thick is not the same as resistant.
Against the code target
Annual energy saved by reaching the target

Air films, cavity values and R per inch are typical published figures, not a design. Real assemblies also lose heat to air leakage, moisture and installation gaps, none of which a series R calculation captures.

Resistances add. Conductances do not.

Heat crossing a wall passes through every layer in turn, so the layers behave like resistors in series: the total thermal resistance is the plain sum of each layer's R-value. Siding, sheathing, cavity fill, drywall, and the thin films of still air clinging to each face all contribute, and the order does not matter to the total.

The U-factor is the reciprocal of that finished sum — U = 1 ÷ R — computed once, at the end. It is the rate of heat flow per unit area per degree, and it is what energy codes outside the United States are usually written in.

The trap is averaging or adding U-factors layer by layer. Because U is a reciprocal, summing the U of each layer gives a number larger than the U of any single layer, which says that adding insulation makes the wall worse. There is no reading of that result that means anything. Sum the R-values, invert once.

The number printed on the batt is not the number in the wall

A roll marked R-19 delivers R-19 through the fibreglass. It delivers nothing like R-19 through the stud sitting next to it. Softwood framing lumber is about R-1.25 per inch, so a 3.5-inch stud is R-4.4 — a quarter of the cavity next to it — and that stud is a continuous path from the drywall to the sheathing.

Framing is also more of the wall than people picture. Counted properly, including plates, corners, headers and the framing around openings, walls built at 16 inches on centre are typically 25% framing by area. Advanced framing at 24 inches with insulated headers gets it down to roughly 18%; ceiling joists are nearer 11%.

The correct treatment is the parallel-path or area-weighted method: compute the U of the cavity path, compute the U of the framing path, weight the two U-factors by their share of the area, then invert. Area-weighting the R-values instead gives a higher, wrong answer, because what conserves per unit of area is heat flow, and heat flow tracks U.

A standard 2×4 wall — vinyl siding, OSB, R-13 batt, drywall, both air films — sums to a nominal R-15.5. The framing path is R-6.9. Weighted at 25%, the wall performs at R-11.8. That 24% is not a rounding error, and almost nothing on the first page of search results accounts for it.

R per inch varies more between products than between categories

Insulation is sold by R-value, but it is manufactured with a conductivity, and the R per inch that follows differs enormously:

MaterialR per inchRSI per inch (25.4 mm)
Blown fibreglass, attic2.2 – 2.70.39 – 0.48
Fibreglass batt3.1 – 3.40.55 – 0.60
Cellulose, loose or dense-pack3.5 – 3.70.62 – 0.65
Open-cell spray foam3.6 – 3.80.63 – 0.67
EPS board3.6 – 4.20.63 – 0.74
Mineral wool batt3.9 – 4.30.69 – 0.76
XPS board4.7 – 5.00.83 – 0.88
Polyisocyanurate board5.6 – 6.50.99 – 1.14
Closed-cell spray polyurethane6.0 – 6.81.06 – 1.20
Softwood framing lumber1.250.22
Dense concrete0.080.014

Ranges come from the U.S. Department of Energy insulation fact sheet and the ASHRAE Handbook of Fundamentals, chapter 26. They are starting points, which is why every R per inch in the calculator is an editable field rather than a hidden constant. Density, ageing, mean temperature and the manufacturer all move the number, and polyiso in particular loses R at low temperature — the direction you least want on a cold night.

R, RSI and the factor of 5.678

R-value is imperial: h·ft²·°F/BTU. RSI is metric: m²·K/W. They describe the same physical property and differ by 5.678. RSI 1.0 is R-5.678; R-30 is RSI 5.28.

That factor is why a Canadian label reading RSI 3.5 and an American label reading R-20 are the same product, and why reading an RSI figure as an R-value understates a wall by nearly a factor of six. This tool shows both at once, along with the metric U-value in W/m²·K, precisely so the two cannot be confused. The conversion is derived from the exact definitions of the BTU, the foot and the degree Fahrenheit, so the round trip closes.

Air films and cavities are free R-value, and they get dropped

A thin layer of still air sticks to every surface and resists heat all by itself. ASHRAE puts the inside film at about R-0.68 on a wall, R-0.61 on a ceiling with heat flowing up and R-0.92 on a floor with heat flowing down — the direction matters, because convection helps a rising flow and fights a falling one. The outside film is about R-0.17 in wind and R-0.25 in still air.

An unvented cavity between 20 and 100 mm adds roughly R-1.0. Give one face a reflective foil and it can approach R-2.8, because most of the heat crossing an air gap travels as radiation and foil refuses to emit it. Note what that means: the foil does nothing on its own. A radiant barrier pressed flat against a surface has no air space to protect and contributes almost nothing.

On a well-insulated wall these items are a small share of the total. On a bare one they can be most of it, which is exactly when leaving them out distorts the comparison you are trying to make.

What the IECC climate zones actually ask for

The prescriptive R-values in the 2021 IECC rise with the zone, and rise much faster for ceilings than for walls:

ZoneCeilingWood-frame wallFloor
1 — Miami, HonoluluR-30R-13R-13
2 — Houston, Orlando, PhoenixR-49R-13R-13
3 — Atlanta, Los Angeles, DallasR-49R-20R-19
4 — Baltimore, Seattle, St. LouisR-60R-30 or R-20+5ciR-19
5 — Chicago, Denver, BostonR-60R-30 or R-20+5ciR-30
6 — Minneapolis, BurlingtonR-60R-30 or R-20+5ciR-30
7–8 — Duluth, FairbanksR-60R-30 or R-20+5ciR-38

Ceilings jump to R-49 in zone 2 while the wall stays at R-13, and the reason is geometry rather than climate: an attic floor is flat, cheap to reach and has unlimited depth, so the code takes the R where the R is easy to get. The wall is expensive per unit of R.

Your jurisdiction may still be enforcing an older edition — many are on the 2018 or 2015 IECC — so treat these as the direction of travel and confirm what your building department has adopted. The target field in the calculator stays editable for that reason.

The attic first, and the reason is not insulation

In a house with an uninsulated or under-insulated attic, the attic is almost always the best dollar spent. Going from R-11 to R-49 in a ceiling removes about 78% of the conducted loss through that surface. Getting the same fractional improvement from a wall means opening it up.

But attic work is only as good as the air sealing under it. Warm air leaks upward through can lights, top plates, plumbing chases and the attic hatch, and insulation that is permeable to air — loose fill and batts both — does not stop that flow. It merely filters it. Blowing R-49 over an unsealed ceiling plane buys much less than the R-value implies, and the dirty streaks visible in old fibreglass are that air passing through it.

Doubling the R does not double the saving

Heat loss through an assembly is proportional to U, and U is 1 ÷ R. Every increment of R therefore removes a smaller slice of what is left:

Each of those steps is a doubling, each costs at least as much as the one before it, and each returns half as much. The calculator shows the next identical step alongside the current one so the shape of that curve is visible instead of implied. Somewhere on it, the money is better spent on air sealing, on the windows, or on a better heating system — and the point where that happens comes far sooner than the marketing suggests.

What a series R-value calculation cannot tell you

Everything stays in your browser

Every figure is computed locally as arithmetic. Nothing is uploaded, nothing is stored and there is no account. The maths lives in a separate module that is verified against hand-worked examples outside the browser, including the parallel-path wall above, so the numbers are checkable rather than merely confident.

Frequently asked questions

Do you add R-values or U-factors when you stack insulation?

You add R-values. Heat crosses the layers one after another, so the resistances add in series exactly like resistors: R total is the sum of every layer. The U-factor is the reciprocal of that finished total, U = 1 ÷ R, calculated once at the end. Adding the U-factors of individual layers is the classic mistake and it produces a U larger than any single layer's, which would mean that adding insulation makes a wall worse. That is physically impossible, and it still shows up in spreadsheets and in more than one calculator.

Why is my R-19 wall not actually R-19?

Because the studs are not insulation. R-19 describes the batt sitting between the framing, but softwood lumber is about R-1.25 per inch and framing occupies roughly 25% of a typical wall built at 16 inches on centre — studs, plates, corners and headers together. Heat takes the easy path through the wood. Weighted by area, a nominal R-15.5 assembly with R-13 batts delivers about R-11.8 in practice, a 24% loss. The calculator computes that parallel path instead of only mentioning that it exists.

What is the difference between R-value and RSI?

They measure the same thing in different units. R is imperial, in h·ft²·°F/BTU. RSI is metric, in m²·K/W. One R-value equals 0.1761 RSI, so RSI 1.0 equals R-5.678. R-30 attic insulation is RSI 5.28, not RSI 30. Reading one as the other is an error of a factor of 5.7 — an order of magnitude, not a rounding difference — and it is the reason a product sold as RSI 2.5 in Canada and R-14 in the United States is the same product.

How much R-value do air films and air gaps add?

More than people expect, and they are free. The still-air film on an inside wall surface is about R-0.68, on a ceiling with heat flowing up about R-0.61, and on a floor with heat flowing down about R-0.92. A windy exterior surface is about R-0.17. An unvented cavity of 20 to 100 mm adds about R-1.0, and the same cavity with one reflective foil face can reach about R-2.8. On an uninsulated wall those items are most of the total resistance, which is why omitting them can understate a bare assembly by half.

If I double the R-value, do I halve my heating bill?

You halve the heat lost through that assembly, which is not the same as halving the bill. Heat loss is proportional to U, not to R, so doubling R from 13 to 26 removes half the loss through that surface. Doubling again from 26 to 52 removes only half of what was left — a quarter of the original. The same amount of added R buys half the result the second time. And the assembly is one of several losses: windows, air leakage and ventilation are untouched by it.

Does this work for steel studs?

Not accurately, and it is important to say so. Steel conducts roughly 400 times better than wood, so the simple parallel-path method significantly overstates a steel-framed wall — a cavity filled with R-13 can perform closer to R-6 or R-7 overall. ASHRAE uses a modified zone method or published correction factors for steel framing. Use the tool for wood framing, masonry and continuous assemblies, and treat any steel-stud number it gives you as an optimistic ceiling rather than an answer.